"W" Series - 48 Volt, 1800 Watts

Series Description: 

We used the rugged and reliable design of our previous model and added the features that you have been asking for... Plus many more!

SPEC SHEET (click here)

Series Features: 

Operation

  • Rotatable LCD Display, easy to read, large 4 line by 20 character backlit display
  • Scrolling Message which lists Relay Status, Alarms and Faults
  • Display shows input and output values including battery % charge
  • Quick Status Screens and Buck/Boost Event and Run Time Counters
  • Keypad for Local Programming
  • Adjustable Transfer Points with Normal and Generator settings
  • Six fully Programmable Dry Relay Contacts w/Low Battery, Timer, and others
  • Event Log of Events, up to 256 events
  • Automatic Low Battery Shutdown

Power

  • Buck/Boost (wide 80-160Vac input range)
  • Pure Sine Wave Inverter, Less than 3%THD, 60Hz ± 0.05%
  • TVSS compliant with ANSI C.62.41.2-2002 (IEEE 587)
  • Self Test
  • Thermally –controlled cooling fan

Charger

  • 4 Step Charger (Zero Volt Start, Bulk, Accept, and Float)
  • Temperature Compensated Charging
  • Charges AGM or Gel Batteries
  • Load Management

Communications

  • Ethernet (IP is user configurable), generates emails
  • Configure and acquire status information by using your favorite web browser
  • RS-232
Output Power: 
1800 @ 25°C, 1200 @ 74°C (Watts continuous)
Output voltage: 
120 VAC regulated (Pure Sine)
Output Frequency: 
60 Hz ± 0.05%
Output Current: 
Up to 15 (Amps AC)
Input Voltage: 
41 to 64 (Volts DC)
Peak Output: 
50 (Amps AC)
Input Current: 
Up to 42 (Amps DC)
Efficiency: 
Up to 86% (Inverter)
Operating Temperature: 
-40°C to 74°C (-40°F to 165°F)
Transfer Time: 
30 (milliseconds) typical
Output Voltage: 
Regulated and temp. compensated
Output Current: 
Up to 15
Input Current: 
Up to 7.6
Charge Time: 
Less than 10 hours to 80% or greater